d
Power Supply
Model
ALPHA/XM31-915-HP
Firmware
V2.06.0
Major Alarm
OK
Minor Alarm
OK
Operational Mode
Line
Charger Mode
Float
Tamper
Door closed
Power Supply Language
English
Power Supply Priority
Normal
d
Input
AC Line Mode
OK
Voltage
117.58
V
Current
4.68
A
Power
505
W
Frequency
60
Hz
Tap Status
Normal
Frequency Range
3.00
Hz
Current Limit
17.00
A
Input Power Consumption
762
Wh
1
Output
Voltage
86.92
V
Power
381
W
Apparent Power
416.34
VA
Frequency
59.98
Hz
Percent Load
31.90
%
Output Setting
90 V
Output Regulation
Coarse override
Over-current Tolerance
3.000
sec
Retry Delay
60
sec
Retry Limit
20
Active Drop Alarm
OK
Active Drop Threshold
50
W
Current
4.79
A
d
Inverter
Inverter Status
Off
End of Discharge Type
String
End of Discharge Level
1.75
V/cell
Reduced Peak Mode
Disable
Total Standby Events
23
Time Since Last Standby Event
22d 13h:48m
Time in Last Standby Event
0d 5h:10m
Total Time in Standby
759
min
Standby Events Since Reset
8
Time in Standby Since Reset
581
min
Time Since Reset
102
day(s)
Total Run Time
102
day(s)
Transformer Run Time
102
day(s)
Total Downtime
0d 0h:00m
Oil Cap Lifespan Consumed
4.1
%
d
Self Test
Deep Discharge Cycle
Timed
Test Countdown
21
day(s)
Test Duration
10
min
Test Interval
30
day(s)
Test Inhibit
No
→ CSV